2 Phase Moulded Case Circuit Breaker

Original
price: Negotiable
minimum:
Total supply:
Delivery term: The date of payment from buyers deliver within days
seat: Zhejiang
Validity to: Long-term effective
Last update: 2019-06-30 07:27
Browse the number: 170
inquiry
Company Profile
 
 
Product details

1. Application Of Moulded Case Circuit Breaker

ZQM1 series moulded case circuit breaker is one of products developed and manufactured by adopting international advanced technology. It is supplied with rated insulating voltage 550 and 800V and used for circuit of AC 50/60Hz, rated operating voltage AC 400V (or below), rated operating current up to 1600A for infrequent changing over and starting of the motors. The products conforms to IEC60947-2 standard.


2. Main Technical Specification (Table1)

Type

Rated

current (A)

Polenum-ber

Ratedinsui-atingvolt-age (V)

Rated

operat-ingvolt-age (V)

Arcing-

over

distance (mm)

Ultimate

short

circuit

breaking

capacity (KA)

Servies

short

circuit

breaking

capacity (KA)

Operation

perform - 

ance

Utiliza - tioncat - egory

Load

Unload

ZQM1-63L

(6),10

16,20

25 ,32

40,50

63

3, 4

500V

400V

0

25

18

1500

8500

A

ZQM1-63M

0

50

35

ZQM1-100L

(10),16

20,25

32,40

50,63

80,100

800V

0(≤50)

35

22

ZQM1-100M

0(≤50)

50

35

ZQM1-100H

0(≤50)

85

50

1000

7000

ZQM1-225L

100,125

160,180

200,225

≤50

35

22

ZQM1-225M

≤50

50

35

ZQM1-225H

≤50

85

50

1000

4000

ZQM1-400L

225,250

315,350

400

≤50

50

35

ZQM1-400M

≤100

65

42

ZQM1-630L

400,500

630

≤100

50

35

ZQM1-630M

≤100

65

42

ZQM1-630H

≤100

100

65

ZQM1-800M

630,700

800

3

≤100

75

50

ZQM1-800H

≤100

100

65

ZQM1-1250M

1000,1250

≤100

100

65

ZQM1-1250H

≤100

125

75

ZQM1-1600M

1600

≤100

150

80


Note:

6A without thermal protection

The N-pole of four-poles breaker is sited at the right side of the product has four types:

Type A: Without current trip-lease on N pole which making all the time, not closing and opening with the other three poles.

Type B: Without current trip-release on N pole which closing and opening with the other poles.

Type C: With current trip-release which closing and opening with the other three poles.

Type D: With current trip-release which making all the time not closing and opening with the other three poles.


3. Protection Characteristic

The thermodynamic release of a circuit breaker provides the feature of inverse time-delay, while the magnetic release is the instantaneous operation as shown on table 2 (distribution circuit breaker) and table 3 (motor protection circuit breaker).


Table 2 Of MCCB

Rated current of release (A)

Thermodynamic release (ambient temperature) land +40°C marine +45°C

Operating current of magnetic release (A)

1.05In (cold state) Inoperative time (h)

1.30In (heat state) Operative time (h)

10≤In≤63

≥ 1

< 1

10In±20%

63<In≤100

≥ 2

< 2

100≤In≤800

≥ 2

< 2

5In±20% 10In±20%


Table 3 Of MCCB

Rated current

Thermodynamic release (ambient temperature) land +40°C marine +45°C

Operating current of magnetic release (A)

Of release (A)

1.0In (cold state) non-trip time (h)

1.20In (heat state) trip time (h)

1.50In (heat state) trip time (h)

7.2In (cold state) trip time (h)

10 ≤ In ≤ 225

≥ 2

<2

≤ 4min

4s < Tp ≤ 10s

12In±20%

225 ≤ In ≤ 630

≤ 8min

6s < Tp ≤ 20s